Mengapa Pengukur Titik Embun Pengering Sangat Penting untuk Sistem Udara Terkompresi?

Why Are Dryer Dew Point Meters Critical for Compressed Air Systems

Tags:

Facebook
Twitter
LinkedIn
Pinterest

Mengapa Pengukur Titik Embun Pengering Sangat Penting untuk Sistem Udara Terkompresi?

Maybe You always battle hidden moisture in compressed air that can cause corrosion, freezing, and product defects. By installing dew point meters, you detect and stop moisture issues before equipment fails.

You can monitor dew point to prevent condensation and protect assets. The HENGKO HG970 series provides continuous dew point readings with 4–20 mA dan Modbus RTU outputs, onboard logging, and diagnostics—so you can close the loop for control and energy savings.

image

Here, this guide explains the causes of moisture, how to choose sensors, where to place them, and how to integrate the HENGKO HG970 so you can act quickly and reduce risk.

Why Measure Dew Point?

Q1: What exactly are you measuring?
A: Dew point is the temperature at which water vapor in your compressed air will condense into liquid. Knowing dew point tells you when and where condensation will occur as air cools along the line.

Q2: What goes wrong if you ignore dew point?
A: Moisture triggers corrosion, fouling, freeze-ups, and product contamination. Typical impacts:

Risk What You See in the Plant Cost/Impact Early Warning via Dew Point
Pipe & valve corrosion Rust flakes, seized valves Leaks, pressure loss, unplanned shutdowns Rising baseline dp
Pneumatic wear & sticking Cylinder pitting, actuator stiction Inconsistent positioning, quality drift dp spikes during load peaks
Freeze in cold zones Icing at outdoor/underground runs Line blockages, safety events dp approaching ambient T
Product contamination Water in coatings, electronics, food/pharma lines Scrap, recalls, audit findings dp excursions above spec

Q3: Where should you place sensors to catch problems early?
A: Measure after dryers, before long/cold runs, and at critical points of use:

Location Why Here? What You Learn
Outlet of dryer Validate dryer performance Is the dryer meeting spec?
After main receiver Check re-evaporation/drain function Is storage adding moisture back?
Start of outdoor/underground header Predict cold-zone condensation Do you need lower dp or heat trace?
Critical tools/process skids (POU) Protect quality-sensitive users Is local treatment working?

Q4: How do you use trends (not just snapshots)?
A: Continuous logging lets you spot slow dryer decline, tower-switch spikes, and seasonal effects. A simple approach:

Trend Pattern Likely Cause Action
Gradual baseline rise Fouled prefilter, saturated desiccant Inspect drains/filters; schedule regeneration
Periodic sharp spikes Twin-tower switching Verify purge/valve timing; add alarm delay
Night/weekend dp increase Low flow regeneration inefficiency Adjust DDS or idle strategy

Q5: How should you set alarms without creating nuisance trips?
A: Use thresholds with hysteresis dan time delay:

Dryer Type Typical Spec Target Alarm Threshold (suggested) Hysteresis Delay
Refrigerated +2…+5 °C dp ≥ +7 °C dp 1 °C 60–180 s
Desiccant (-40) ≤ -40 °C dp ≥ -35 °C dp 2 °C 60–180 s
Desiccant (-70) ≤ -70 °C dp ≥ -65 °C dp 2 °C 60–180 s

Q6: What do you do when alarms occur?
A: Follow a short, repeatable checklist:

Step What to Check Pass/Fail Gate
Drains Auto drains cycling? Manual drains clear? If blocked → clean/replace
Prefiltration Coalescer ΔP/condition If oil carryover → change elements, fix compressor
Dryer Regeneration timing/heater/purge If abnormal → service per OEM
Lingkungan Sudden ambient drop/line cold spots Add insulation/heat trace as needed

Q7: How do you verify accuracy?
A: Commission new meters in parallel with a known reference for 2–4 weeks; perform periodic handheld spot checks at the same tap to validate readings and locate dead legs.

Q8: How do you keep people aligned?
A: Document who watches, who acts, and how:

Role Responsibility Tooling/Access
Operations Daily trend review, acknowledge alarms HMI/SCADA, alarm dashboard
Pemeliharaan Executes checklist & repairs Work orders, spare probes/elements
Quality/EHS Audits logs, verifies conformance (ISO 8573) Reports, calibration certs

How Do Dew Point Meters Work?

Q1: Which sensor principles should you consider?
A: Choose by required accuracy, response, and contamination tolerance.

Jenis Sensor Principle (What It Senses) Best Use Case Typical Accuracy
Cermin dingin Mirror cooled until condensation appears Reference labs, calibration standards ±0.1 °C dp
Capacitive Dielectric change with absorbed moisture Fast inline plant monitoring ±1–2 °C dp
Aluminum oxide Conductivity change as moisture adsorbs Budget monitoring, non-critical utilities ±2–3 °C dp

Q2: How do you protect sensors from fouling?
A: Oil aerosols, particulates, and corrosives shorten life. Use coalescing prefilters, particulate screensdan sample conditioning (heated lines or bypass chambers) in wet/dirty streams.

Q3: What outputs and protocols matter for control and diagnostics?
A:

  • 4–20 mA: rock-solid for PLC control and alarms.
  • Modbus RTU: multi-parameter telemetry (dew point, temperature, probe status, sensor health).

Q4: How do you plan calibration and validation?
A: Schedule per sensor type and cleanliness; log offsets from parallel checks and keep certs with your quality records.

Activity Interval (Typical) Notes
Inline spot-check Quarterly Handheld at same tap
Full calibration 6–12 months Traceable standard, more frequent in oily lines
After upset/repair Event-based Re-verify after dryer service or major excursion

Q5: Where does HENGKO HG970 fit?
A: HG970 combines a robust sensing module with 4–20 mA dan Modbus RTU, onboard loggingdan health metrics. Modular probe heads simplify swap-outs to minimize downtime.

Key Features and How to Specify Them

Q1: What ranges/accuracy do you actually need?

Dryer Type Recommended Measurement Range Minimum Accuracy to Specify
Refrigerated +10 … -5 °C dp ±1–2 °C dp
Desiccant (-40 class) 0 … -60 °C dp ±2 °C dp
Desiccant (-70 class) -20 … -80 °C dp ±2 °C dp or better

Q2: Which features reduce lifecycle cost (not just CapEx)?

Fitur Why It Matters What to Ask the Vendor For
Dual output (4–20 mA + Modbus) Control dan rich diagnostics Register map, scaling, status bits
Onboard logging Root-cause analysis, audit trail Download format, capacity, interval options
Replaceable sensor heads Fast maintenance, less downtime Hot-swap design, spare availability
IP-rated enclosure Survives dust/oil/washdown IP65/67 ratings, cable glands
Alarm logic on-probe Local failsafe if PLC/HMI down Setpoints, hysteresis, delay

Q3: How do you turn requirements into a procurement checklist?

Item Your Minimum Stretch/Ideal Notes
Measurement range ___ ___ Match dryer class
Accuracy & traceability ___ ___ ISO-traceable certs required?
Outputs 4–20 mA + Modbus RTU HMI trending + PLC alarms
Logging 30–90 days 180+ days CSV/JSON export
Enclosure IP65 IP67 Ambient/condensing conditions
Serviceability Replaceable head Hot-swap Spare kits stocked
Calibration plan 12 mo 6–12 mo Depends on air cleanliness

HG970 fit: Modular heads, diagnostics, modern I/O, and logging—designed to hit the “Stretch/Ideal” column for many plants.

image

What Mix of Meters Should You Deploy?

Q1: Handheld vs. inline vs. networked—how do you choose?

Option Strengths Limits Best Use
Handheld meter Low CapEx, flexible, great for audits Labor-intensive, snapshot only Commissioning, troubleshooting, spot-checks
Inline transducer Continuous data, closes control loop Per-point cost Critical lines, dryer outlet, cold zones
Networked system Plant-wide view, trends, centralized alarms Integration effort Multi-point analysis, quality & energy mgmt

Q2: How do you protect and install probes for reliability?

Condition Protection/Method Mounting Tip
Oily/dirty air Coalescing prefilter + particulate screen Install upstream and add ΔP gauge
Wet/condensing sample Heated line or bypass chamber Keep flow constant; avoid low points
Critical uptime Dual redundant probes with 3-valve manifold Enables swap without process shutdown

Q3: What’s a simple commissioning plan that works?

Week Task Output
0 Parallel run with reference Offset baseline
1 Verify alarm thresholds/hysteresis/delay Stable alarm behavior
2 Review trends; adjust placement if spikes persist Optimized tap location
4 Lock response checklist; train operators SOP + trained crew

Q4: How do you think about total cost (TCO), not just price?

Cost Component Handheld-only Inline (per point) Networked (per site)
Instrument & accessories $ $$ $$$
Calibration & spares $ $$ $$
Labor (audits/response) $$ $ $
Downtime avoided (benefit) $$ $$$
Energy saved via right-drying $–$$ $$–$$$

Rule of thumb: if moisture excursions cost more than one probe per year, inline monitoring pays for itself.

Q5: How do you integrate HG970 with PLC/SCADA fast?

Signal/Map Example (HG970) Use in Control
4–20 mA (dew point) 4 mA = -80 °C, 20 mA = +20 °C Analog alarm, dryer PID/feed-forward
Modbus holding reg. 40001 = dew point (0.1 °C) Precise trending, reports
Modbus status bits Probe OK, sensor health Maintenance alerts, bad-data suppression
On-probe alarms SP1 = -35 °C, 90 s delay Local interlock if PLC offline

Kesimpulan

You prevent condensation, protect equipment, and save energy when you select, place, and integrate dew point meters correctly. The HENGKO HG970 series offers the accuracy, connectivity, logging, and diagnostics you need for reliable plant monitoring—without over-drying or surprise moisture events.